Contents
- 1. How Heat Pumps Work: COP, Flow Temperature, and Heat Demand
- 2. Leading Heat Pump Models for London Residential Installations
- 3. Boiler Upgrade Scheme (BUS): Grant Eligibility and Process
- 4. Radiator Sizing for Heat Pump Systems in London Period Homes
- 5. Planning and Installation Requirements for Heat Pumps in London
- 6. Costs for Heat Pump Installation in London
- 7. Frequently Asked Questions
How Heat Pumps Work: COP, Flow Temperature, and Heat Demand
AN AIR SOURCE HEAT PUMP OPERATES ON THE REFRIGERATION CYCLE — IT EXTRACTS HEAT ENERGY FROM OUTDOOR AIR (DOWN TO -20°C IN SOME MODELS) AND TRANSFERS IT INTO THE HEATING SYSTEM AND HOT WATER CYLINDER AT A HIGHER TEMPERATURE. THE RATIO OF HEAT OUTPUT TO ELECTRICAL INPUT IS THE COEFFICIENT OF PERFORMANCE (COP). A HEAT PUMP WITH A COP OF 3.0 DELIVERS 3 UNITS OF HEAT FOR EVERY 1 UNIT OF ELECTRICITY CONSUMED — AT CURRENT UK ENERGY PRICES (ELECTRICITY APPROXIMATELY 25P/KWH, GAS APPROXIMATELY 5P/KWH), A COP OF 3.0 GIVES A HEAT PUMP FUEL COST EQUIVALENT TO A GAS BOILER AT 60% EFFICIENCY — I.E., COMPARABLE. AT A COP OF 4.0 (ACHIEVABLE IN MODERATE WINTER CONDITIONS), THE HEAT PUMP COSTS APPROXIMATELY THE SAME AS GAS. THUS THE ECONOMICS OF HEAT PUMPS ARE MARGINAL UNLESS OPERATING AT HIGH COP.
CRITICAL RELATIONSHIP BETWEEN FLOW TEMPERATURE AND COP: THE SINGLE MOST IMPORTANT FACTOR DETERMINING HEAT PUMP COP IS THE FLOW TEMPERATURE OF THE HEATING SYSTEM. HEAT PUMPS ACHIEVE HIGHER COP AT LOWER FLOW TEMPERATURES (THE CLOSER THE OUTPUT TEMPERATURE IS TO THE INPUT AIR TEMPERATURE, THE LESS WORK THE COMPRESSOR MUST DO). A HEAT PUMP ACHIEVING COP 4.0 AT 35°C FLOW TEMPERATURE MAY ACHIEVE ONLY COP 2.5 AT 55°C FLOW TEMPERATURE. THEREFORE, THE DESIGN PRINCIPLE IS TO MINIMISE THE REQUIRED FLOW TEMPERATURE FOR THE HEATING SYSTEM — ACHIEVED BY: (A) REDUCING BUILDING HEAT DEMAND THROUGH FABRIC INSULATION (LOFT, WALLS, FLOORS); AND (B) INCREASING RADIATOR EMITTER SIZE SO THAT EACH RADIATOR CAN DELIVER THE REQUIRED HEAT OUTPUT AT A LOWER FLOW TEMPERATURE.
HEAT DEMAND ASSESSMENT: BEFORE SPECIFYING A HEAT PUMP FOR A LONDON VICTORIAN TERRACE, A HEAT LOSS CALCULATION (BS EN 12831 METHODOLOGY) IS REQUIRED TO DETERMINE THE DESIGN HEAT DEMAND OF THE PROPERTY IN KW. THIS IS THE CRITICAL STEP THAT MANY POORLY SPECIFIED HEAT PUMP INSTALLATIONS SKIP — UNDERSIZED HEAT PUMPS CANNOT MAINTAIN COMFORT IN COLD WEATHER, AND OVERSIZED HEAT PUMPS OPERATE INEFFICIENTLY DUE TO SHORT-CYCLING. THE MCS INSTALLER STANDARDS (MCS 020) REQUIRE A HEAT LOSS CALCULATION FOR EVERY HEAT PUMP INSTALLATION.
Leading Heat Pump Models for London Residential Installations
THE FOLLOWING HEAT PUMP MODELS ARE THE MOST SPECIFIED FOR LONDON RESIDENTIAL INSTALLATIONS AS OF 2025, COMBINING PERFORMANCE, COLD-WEATHER CAPABILITY, RELIABILITY, AND PARTS/SERVICE AVAILABILITY.
VAILLANT AROTHERM PLUS (5KW, 7KW, 10KW, 12KW): THE MARKET-LEADING RESIDENTIAL HEAT PUMP IN THE UK. THE AROTHERM PLUS IS A MONOBLOCK UNIT (THE ENTIRE REFRIGERANT CIRCUIT IS IN THE OUTDOOR UNIT — ONLY WATER PIPEWORK CONNECTS TO THE INDOOR UNIT, SIMPLIFYING INSTALLATION). RATED COP: 4.2 AT A7/W35 (7°C OUTDOOR AIR, 35°C FLOW — THE EUROPEAN TEST CONDITION). COLD-WEATHER PERFORMANCE: COP 2.2 AT A-7/W35 (-7°C AIR). FULL OUTPUT TO -15°C AMBIENT. SMART SYSTEM COMPATIBILITY: VAILLANT SENSOCOMFORT 720F (WEATHER COMPENSATION, ROOM TEMPERATURE CORRECTION, APP CONTROL). THE AROTHERM PLUS IS TYPICALLY PAIRED WITH A VAILLANT UNISTORE 200 OR 300 LITRE STAINLESS STEEL UNVENTED HOT WATER CYLINDER (FOR DOMESTIC HOT WATER AT 60°C PASTEURISATION TEMPERATURE TO MANAGE LEGIONELLA RISK).
DAIKIN ALTHERMA 3 H MT HPM (4KW TO 16KW — HIGH-TEMPERATURE VERSION): THE DAIKIN ALTHERMA 3 H MT (MEDIUM TEMPERATURE) OPERATES EFFICIENTLY UP TO 65°C FLOW TEMPERATURE — SIGNIFICANTLY HIGHER THAN STANDARD ASHPS (TYPICALLY LIMITED TO 55°C). THIS MAKES IT SUITABLE FOR LONDON PERIOD PROPERTIES WHERE RADIATORS ARE NOT YET REPLACED AND EXISTING PIPEWORK WAS DESIGNED FOR HIGH-TEMPERATURE GAS BOILER OPERATION. THE COMPROMISE IS LOWER COP AT HIGH FLOW TEMPERATURES. THE STANDARD ALTHERMA 3 H (LT — LOW TEMPERATURE) IS MORE EFFICIENT AT 35-45°C AND IS APPROPRIATE WHERE RADIATORS HAVE BEEN UPGRADED OR WHERE UFH IS INSTALLED.
WORCESTER BOSCH HEAT PUMP T600 (5KW, 8KW, 12KW): RELEASED AS WORCESTER BOSCH'S FIRST MONOBLOC ASHP. THE T600 IS COMPATIBLE WITH THE WORCESTER BOSCH GREENSTAR RANGE CONTROLS AND IS BACKED BY THE WORCESTER BOSCH INSTALLER NETWORK (IMPORTANT FOR LONG-TERM SERVICE). COP RATED AT 3.9 AT A7/W35.
MITSUBISHI ELECTRIC ECODAN (4.5KW TO 16KW): ECODAN IS THE LONGEST-ESTABLISHED ASHP RANGE IN THE UK RESIDENTIAL MARKET AND HAS A STRONG RELIABILITY RECORD. THE R32 REFRIGERANT MODELS (PUHZ-SW ECODAN) ARE THE CURRENT GENERATION. THE LOSSNAY CYLINDER (MCC SERIES) INTEGRATES HEAT PUMP AND CONTROL INTO A COMPACT INDOOR CYLINDER UNIT.
Boiler Upgrade Scheme (BUS): Grant Eligibility and Process
THE BOILER UPGRADE SCHEME (BUS) IS THE MAIN GOVERNMENT GRANT FOR HEAT PUMP INSTALLATION IN ENGLAND AND WALES, ADMINISTERED BY OFGEM. THE GRANT VALUE IS £7,500 FOR AN AIR SOURCE HEAT PUMP OR A GROUND SOURCE HEAT PUMP (INCREASED FROM £5,000 IN OCTOBER 2023).
ELIGIBILITY CRITERIA FOR THE BUS GRANT: THE PROPERTY MUST BE IN ENGLAND OR WALES. THE PROPERTY MUST HAVE AN EPC (ENERGY PERFORMANCE CERTIFICATE) THAT IS NO MORE THAN 10 YEARS OLD AND MUST NOT HAVE AN OUTSTANDING RECOMMENDATION FOR LOFT INSULATION OR CAVITY WALL INSULATION (PROPERTIES THAT CAN BE INSULATED MUST BE INSULATED BEFORE RECEIVING THE GRANT). THE EXISTING HEATING SYSTEM MUST BE A GAS OR OIL BOILER, OR ELECTRIC DIRECT HEATING — NOT ANOTHER HEAT PUMP (A HEAT PUMP CANNOT REPLACE ANOTHER HEAT PUMP UNDER BUS). THE INSTALLATION MUST BE BY AN MCS (MICROGENERATION CERTIFICATION SCHEME) CERTIFIED INSTALLER USING AN MCS-CERTIFIED HEAT PUMP.
PROCESS: THE MCS-CERTIFIED INSTALLER APPLIES FOR THE GRANT VOUCHER ON BEHALF OF THE HOMEOWNER BEFORE INSTALLATION. THE VOUCHER IS VALID FOR 3 MONTHS. AFTER INSTALLATION AND MCS CERTIFICATE ISSUE, THE INSTALLER CLAIMS THE GRANT DIRECTLY FROM OFGEM AND DEDUCTS THE £7,500 FROM THE CUSTOMER'S INVOICE. THE HOMEOWNER DOES NOT NEED TO APPLY — THE INSTALLER HANDLES THE PROCESS.
PRACTICAL NOTE FOR LONDON PROPERTIES: LONDON VICTORIAN TERRACES WITH SOLID BRICK WALLS (NO CAVITY FOR INSULATION) ARE NOT EXCLUDED FROM THE BUS EVEN IF WALL INSULATION IS NOT INSTALLED — SOLID WALL INSULATION IS NOT A STANDARD EPC RECOMMENDATION IN THE SAME WAY AS CAVITY WALL INSULATION. HOWEVER, THE EPC MUST NOT FLAG OUTSTANDING LOFT INSULATION. CHECK YOUR CURRENT EPC FOR RECOMMENDATIONS BEFORE APPLYING.
Radiator Sizing for Heat Pump Systems in London Period Homes
THE MOST TECHNICALLY DEMANDING ASPECT OF HEAT PUMP INSTALLATION IN A LONDON VICTORIAN TERRACE IS RADIATOR ADEQUACY. A CONVENTIONAL GAS BOILER SYSTEM OPERATES AT DELTA T = 20°C (80°C FLOW, 60°C RETURN). THE HEAT OUTPUT OF A RADIATOR IS RATED AT DELTA T 50 (MEAN WATER TEMPERATURE 70°C IN A ROOM AT 20°C — EUROPEAN STANDARD RATINGS). WHEN AN ASHP OPERATES AT LOWER TEMPERATURES (E.G., 45°C FLOW, 35°C RETURN, MEAN WATER TEMPERATURE 40°C), THE RADIATOR OUTPUT IS SUBSTANTIALLY REDUCED.
RADIATOR OUTPUT AT REDUCED TEMPERATURE: AT 40°C MEAN WATER TEMPERATURE (45/35 SYSTEM) COMPARED TO 70°C DELTA T 50 RATING, A RADIATOR DELIVERS APPROXIMATELY 41% OF ITS RATED OUTPUT. THEREFORE, A ROOM PREVIOUSLY HEATED BY A 2.0KW (DELTA T 50) RADIATOR WILL RECEIVE ONLY 0.82KW HEAT OUTPUT FROM THE SAME RADIATOR AT HEAT PUMP SYSTEM TEMPERATURES.
SOLUTION: REPLACE UNDERSIZED RADIATORS WITH APPROPRIATELY SIZED UNITS. FOR EACH ROOM, THE HEAT LOSS (KW) IS CALCULATED AND A RADIATOR SELECTED THAT DELIVERS THAT OUTPUT AT 45°C MEAN WATER TEMPERATURE. THIS TYPICALLY REQUIRES EITHER DOUBLE-PANEL DOUBLE-CONVECTOR (K2 TYPE 22) RADIATORS IN LARGER SIZES THAN THE EXISTING, OR LOW-SURFACE-TEMPERATURE (LST) RADIATORS FOR CHILD-SAFE APPLICATIONS.
ALTERNATIVELY, LOW-TEMPERATURE HEAT PUMPS WITH WEATHER COMPENSATION: IF RADIATORS CANNOT BE REPLACED (E.G., IN A RENTED PROPERTY OR WHERE CONSTRAINTS PREVENT WORKS), THE DAIKIN ALTHERMA 3 H MT (HIGH TEMPERATURE VERSION) CAN OPERATE AT 55 TO 65°C FLOW TEMPERATURE WITH THE ORIGINAL RADIATORS — BUT AT REDUCED COP. THIS IS A VALID INTERIM STRATEGY.
Planning and Installation Requirements for Heat Pumps in London
AIR SOURCE HEAT PUMP INSTALLATION IN ENGLAND IS GENERALLY PERMITTED DEVELOPMENT — NO PLANNING PERMISSION IS REQUIRED FOR A STANDARD RESIDENTIAL INSTALLATION PROVIDED SPECIFIC CONDITIONS ARE MET.
PERMITTED DEVELOPMENT CONDITIONS FOR ASHP: THE UNIT MUST NOT EXCEED 0.6M' VOLUME. THE UNIT MUST NOT BE INSTALLED ON A WALL OR ROOF FACING A HIGHWAY. ONLY ONE HEAT PUMP PER DWELLING IS PERMITTED UNDER PD. THE PROPERTY MUST NOT BE A LISTED BUILDING OR WITHIN THE CURTILAGE OF A LISTED BUILDING. IN A CONSERVATION AREA, THE UNIT MUST NOT BE ON THE PRINCIPAL ELEVATION (FRONT) OR A SIDE ELEVATION VISIBLE FROM A HIGHWAY. THE INSTALLATION MUST NOT RESULT IN THE TOTAL NOISE LEVEL EXCEEDING MCS HEAT PUMP NOISE REQUIREMENTS.
NOISE CONSIDERATIONS: THE HEAT PUMP MUST COMPLY WITH MCS 020 NOISE POSITION REQUIREMENTS — THE UNIT MUST BE POSITIONED AT LEAST 1M FROM NEIGHBOURING PROPERTY WALLS (FENCES AND BOUNDARIES) AND THE PREDICTED SOUND LEVEL SHOULD NOT EXCEED 42 DB(A) AT 1M IN FRONT OF THE UNIT. IN LONDON TERRACES WITH NARROW SIDE RETURNS AND SMALL REAR GARDENS, POSITIONING A HEAT PUMP UNIT THAT MEETS BOTH NOISE AND PLANNING CRITERIA IS A SPECIFIC DESIGN CHALLENGE. THE INSTALLER MUST PROVIDE A NOISE ASSESSMENT AS PART OF THE MCS INSTALLATION CERTIFICATION.
PART L COMPLIANCE: ALL NEW HEATING SYSTEMS IN EXISTING DWELLINGS (INCLUDING HEAT PUMP REPLACEMENTS) MUST COMPLY WITH BUILDING REGULATIONS PART L (CONSERVATION OF FUEL AND POWER). HEAT PUMPS AUTOMATICALLY SATISFY PART L MINIMUM HEATING SYSTEM EFFICIENCY REQUIREMENTS. HOWEVER, THE HOT WATER CYLINDER AND CONTROLS MUST ALSO COMPLY WITH PART L — AN UNVENTED CYLINDER WITH A MINIMUM 45MM FACTORY-APPLIED INSULATION JACKET AND A WEATHER-COMPENSATING THERMOSTAT CONTROL ARE REQUIRED.
Costs for Heat Pump Installation in London
HEAT PUMP INSTALLATION COSTS IN LONDON ARE HIGHER THAN THE UK AVERAGE DUE TO LABOUR RATES AND THE ADDITIONAL COMPLEXITY OF LONDON PERIOD PROPERTIES.
TYPICAL TOTAL INSTALLED COST FOR AN ASHP IN A 3-BEDROOM LONDON VICTORIAN TERRACE (INCLUDES: HEAT PUMP UNIT, HOT WATER CYLINDER, ALL PIPEWORK, CONTROLS, ELECTRICAL CONNECTIONS, DECOMMISSION OF EXISTING BOILER, COMMISSIONING, AND MCS CERTIFICATE): £10,000 TO £18,000 BEFORE GRANT. AFTER £7,500 BUS GRANT: £2,500 TO £10,500 CUSTOMER COST.
ADDITIONAL COSTS WHERE RADIATOR REPLACEMENT IS REQUIRED: £100 TO £300 PER RADIATOR (SUPPLY AND FIT) — FOR A 3-BEDROOM TERRACE WITH 8 RADIATORS, ADD £800 TO £2,400. BUFFER TANK (REQUIRED BY SOME HEAT PUMP MANUFACTURERS WHERE THE HYDRONIC SYSTEM VOLUME IS TOO SMALL): £200 TO £400 FOR A 50 TO 100 LITRE BUFFER VESSEL.
GROUND SOURCE HEAT PUMP (GSHP): SIGNIFICANTLY MORE EXPENSIVE AND RARELY PRACTICAL IN LONDON BECAUSE THE BOREHOLE OR GROUND LOOP INSTALLATION REQUIRES SIGNIFICANT GARDEN ACCESS AND EXCAVATION OR DRILLING. A GSHP SYSTEM TYPICALLY COSTS £20,000 TO £45,000 INSTALLED — SUITABLE FOR LARGER LONDON DETACHED OR SEMI-DETACHED PROPERTIES WITH GARDEN ACCESS FOR GROUND LOOPS.
RUNNING COST COMPARISON: FOR A TYPICAL 3-BEDROOM LONDON TERRACE WITH 12,000 KWH/YEAR HEAT DEMAND: GAS BOILER AT 89% EFFICIENCY: 13,483 KWH GAS X 5P = £674/YEAR. ASHP AT COP 3.0: 4,000 KWH ELECTRICITY X 25P = £1,000/YEAR. ASHP AT COP 3.5 (REALISTIC SEASONAL AVERAGE FOR LONDON CLIMATE): 3,429 KWH ELECTRICITY X 25P = £857/YEAR. WITH OCTOPUS COSY TARIFF (HEAT PUMP OPTIMISED OFF-PEAK RATES): POTENTIALLY 15-25% CHEAPER THAN STANDARD RATE.
Frequently Asked Questions
Is my London Victorian terrace suitable for a heat pump?▼
How much is the heat pump grant and who applies for it?▼
What is the seasonal COP I can expect from a heat pump in London?▼
Do I need planning permission for an air source heat pump in London?▼
Can a heat pump also provide hot water?▼
Important Note
This guide is for general information only. Building regulations, planning rules, and legal requirements change regularly and vary by local authority. Always seek professional advice specific to your project and location. RCB Design & Build offers free initial consultations — book your free survey.